KOLD KATCHER INC. - HEAT TRACING SYSTEMS
Box 306 Standard, Alberta, Canada T0J 3G0
PH: (403) 644-2268     FAX: (403) 644-2267



TECHNICAL DATA

DESIGN SPECIFICATIONS

Model HT – 24 (Base Model) Information

Construction Materials
Frame..........................................................................................Aluminum
Fluid reservoir.................................................................leak tested @ 210 kpa
Gas capture chamber....................................................leak tested @ 210 kpa
Exchanger guard...................……………………………….................Aluminum

Fittings
Hi-temp shutdown valve (factory set)…………………….……..93 degrees Celsius
Fluid return throttle valve-with built in by-pass(factory set)…….40 degrees Celsius
Pressure cap on fluid reservoir………………………………………………....48kpa
Gas capture chamber-Relief valve…………………………………………….35 kpa
Threaded fittings (painted)………………………………………2000 lb forged steel
Tubing and fittings……………………………………………………..stainless steel
Heat exchanger……………………………................stainless steel ASME rated

Pump – Non Lubricated
Maximum operating pressure………………………………………………..690 kpa
Operating temperature range………………………….……-40 to 65 degrees Celsius
Flow rate (@60 SPM)……………………………………………….4.5 liters/minute

24” x 24” – Mark II Flush Mount Catalytic Heater
Heat input……………………………………………………………..16,000 Btu/hr.
Face temp. of heater @ maximum output…………………….…370 degrees Celsius
Gas consumption @ maximum output……………………………………16 SCF/Hr.

Dry Weight of Unit……………………………………………………..Approx.70 Kgs.
Fluid capacity (500’ of 3/8” or 1/2" tubing)…………………………10-12 liters
Fluid reservoir-Working volume…………………………………………….1.4 liters
Fluid reservoir expansion volume……………………………………………1.2 liters

Circulation Fluid
Kold Snap-40TM Heat Transfer Fluid.....................................no mixing required

Maintenance Schedule
Circulation Fluid.........................................................Replace every 2 years Pump Servicing....................................................................Suggested every 2 years
Service and maintenance available from KoldKatcher. Contact us at: (403) 644-2268.

AVAILABLE OPTIONS

MODEL
HT 12
HT 24
HT 48
BTU/Hour
8000
16000
32000
Max. Ft. Heat Trace
250'
500'
1000'
Compact Design
 
Aluminum Frame
Powder Coated Cabinet
 
Insulated All Weather Enclosure
Building/Skid Mount
 
 
 
Remote Monitoring & Control

*Custom Models Available

Standard Items Include:
  • One year full parts warranty
  • Factory set high temp. shutdown
  • Thermal control valve
  • Spill containment
  • Exchanger guard
  • 25' Electrical starter cable
  • Catadyne exhaust vent shroud
Optional Items:
  • NEW- REMOTE MONITORING AND CONTROL FUNCTIONS
Desiccant Dryer    Particulate Filter    Flow Indicator   

Thermal Divert Valve    Regulators    Low Level Shutdown